A robust damping controller for SMES using loop-shaping technique

A robust damping controller for a power system installed with super-conducting magnetic energy storage (SMES) has been designed using a simple graphical loop-shaping technique. The graphical method starts by selection of a nominal plant function satisfying the robust stability and performance criter...

Full description

Saved in:
Bibliographic Details
Main Author: Rahim, A.H.M.A. (author)
Other Authors: unknown (author)
Format: article
Published: 2005
Subjects:
Online Access:https://eprints.kfupm.edu.sa/id/eprint/595/1/robust_damping_controller_for_SMES_using_loop.pdf
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:A robust damping controller for a power system installed with super-conducting magnetic energy storage (SMES) has been designed using a simple graphical loop-shaping technique. The graphical method starts by selection of a nominal plant function satisfying the robust stability and performance criterion. The variations in operating conditions from the nominal values are modeled as multiplicative structured uncertainty. The generator-SMES system has been represented with a detailed dynamic model for the control design. The robust design, with generator speed variation as the controller input, was tested for a range of operating points considering various disturbances. It is observed that the fixed parameter robust controller provides very good damping for a wide range of operating conditions.