In order to perform micro-PIXE measurements on water trees in underground HV cables when a large number of cable samples are involved, a sequence of tests has been devised to minimize time and effort for sample preparation, water tree detection and analysis. These tests include electrical diagnostic...

وصف كامل

محفوظ في:
التفاصيل البيبلوغرافية
المؤلف الرئيسي: Al-Hamouz, Z. (author)
مؤلفون آخرون: unknown (author)
التنسيق: article
منشور في: 2006
الموضوعات:
الوصول للمادة أونلاين:https://eprints.kfupm.edu.sa/id/eprint/682/1/pdf_682.pdf
الوسوم: إضافة وسم
لا توجد وسوم, كن أول من يضع وسما على هذه التسجيلة!
الوصف
الملخص:In order to perform micro-PIXE measurements on water trees in underground HV cables when a large number of cable samples are involved, a sequence of tests has been devised to minimize time and effort for sample preparation, water tree detection and analysis. These tests include electrical diagnostic tests to predict the possible presence of water trees, optical microscopy on cable insulation to detect water trees in the samples screened by the electrical tests, scanning electron microscopy for detailed surface topography of water trees, and nuclear microscopy for elemental composition and distribution maps of water trees. Correlations among the results of the four types of measurements are discussed to evaluate the usefulness of the methodology